Search by SeriesWSP SeriesSignal ConvertersSearch by FunctionTemperature Converters
WSP-RTW

2-output RTD temperature converter(Response time:25ms)
Converter which outputs DC signal proportional to the Pt100Ω/JPt100Ω/Ni508.4Ω RTD signals (2-output)
Delivery: Inquiry
Features
Easy maintenance by plug-in structure
Download
Date Sheets
Manuals
Dimensions
Specifications
| Input | Tempereature(Pt100Ω/JPt100Ω/Ni508.4Ω RTD) |
|---|---|
| Output | DC voltage/DC current(2-output) |
| Power | AC100~240V ±10% DC24V ±10% DC10.8~30V DC110V ±10% |
| Accuracy | ±0.1%fs |
| Response time(0→90%) | 25ms |
| Zero-Span adjustment | ±10%fs(15 turn trimmer) |
| Dielectric strength | AC3000V |
| Weight | Approx.150g |
| Dimensions(HWD) | 84×29.5×106.5mm |
| Operating temperature/humidity | -5~+55℃ Lower limit 90%RH |
| Standards & Approvals | EN61326-1 EN61010-1 EN IEC 63000 |